What a Swiss hotel must inspect, and when.

The regulations say «regelmässig» more often than they say a number. This is the list we keep — with the numbers where they exist, and honesty where they don't. Free to use, with or without us.

2026
A · Fire & life safety
InspectionIntervalBasisNotes
Integral test, all fire systems4 yearsVKF 108-15 §7.4Accommodation = risk group 2
Fire detection, function testyearly ‡EN 54 / mfr.
Emergency & escape lighting2 × yearlyVKF 17-151× with self-monitoring
Extinguishersyearly †EN 3 / insurer
Wall hydrants / hose reelsyearly ‡EN 671-3
Smoke & heat extraction (RWA)yearly ‡VKF 21-15
Fire doors & dampersyearly †VKF 108-15Included in integral-test years
Evacuation drillyearly †VKF 12-15«Regularly» in law; we set yearly
Staff instructionyearly + onboardingVKF 12-15New staff within first month
B · Building systems
InspectionIntervalBasisNotes
Electrical installation (NIV)5 years †NIV Art. 36Hotels commonly in the 5-year bracket
Lift, statutory inspection2 years †SR 930.112 / SVTIPlus mfr. maintenance contract
Heating plant, burner serviceyearly ‡mfr. / canton
Pressure vessels / expansion5 years †SVTI
Emergency generatormonthly run · yearly load †insurer / SIAWhere fitted
Roof, façade & drainageyearlygood practiceAfter storms additionally
C · Water, air & kitchen
InspectionIntervalBasisNotes
Legionella: temperaturesmonthlySVGW W3/E †60°C boiler / 55°C circulation
Legionella: lab samplingyearly †FSVO guidanceShower heads, distal points
Ventilation plant & filtersyearly ‡SWKI / mfr.
Kitchen extraction, degreaseyearly · heavy use 6 mo. †VKF / insurerThe classic hotel fire path
Grease separatorper volume ‡municipal
Backflow preventersyearly †SVGW
D · Standing duties
InspectionIntervalBasisNotes
The evidence file itselfcontinuousVKF 108-15 §7.5Dated, named, signed, findable
Permit conditions reviewyearlyyour permitConditions outlive the people who accepted them
Insurance questionnaireat renewalpolicyAnswers age faster than buildings
Contractor certificatesat each visitgood practiceLiability follows the paper trail

Interval set by canton, permit or insurer — the number shown is common practice, not a federal rule. Per manufacturer specification. The interval that applies to your house is fixed by your permit, your canton and your insurer — pinning those down is the first afternoon of the dossier.